Terminations

Terminations upto 36 kV For Single Core XLPE/EPR Insulated

XS OS/ES-2236

DENSONS HEAT SHRINKABLE TERMINATIONS UPTO 36 kV For Single Core XLPE/EPR Insulated Cable

Enquire Now

Features

  • All key inputs are produced in-house.
  • Continuous operation temperature-55oC to 120oC.
  • Corrosion resistant and unlimited shelf life.
  • In compliance with IEC-60502-4 / IS-13573.
  • Electrolytic grade connectors.
Terminations upto 36 kV For Single Core XLPE/EPR Insulated

In conformance with IEEE-48,
VDE 0278 & IS: 13573

Specifications:

Test Item of Heat Shrinkable Termination as per IEC-60502-4 / IS:13573

Testing Items U o/U 6.35/11 kV 12.7/22 kV 19/33 kV
A.C. withstand test 29kV, 5min, no flashover 58kV, 5min, no flashover 86kV, 5min, no flashover
Partial discharge test 11kV < 10pc (Max.) 22kV < 10pc (Max.) 33kV < 10pc (Max.)
Thermal Cycles (63 cycles) under 95-100oC 16kV under 95-100o C 32kV under 95-100o C 48kV
Impulse voltage test 75kV no flashover 125kV no flashover 170kV no flashover
A.C. with stand test 16kV, 15 min, no flashover 32kV, 15 min, no flashover 48kV, 15 min, no flashover
Humidity test (Indoor) No flashover, tracking erosion or mechanical damage occured at 300hrs, 8kV No flashover, tracking erosion or mechanical damage occured at 300hrs, 16kV No flashover, tracking erosion or mechanical damage occured at 300hrs, 24kV
Salt Fog test (Outdoor) No flashover, tracking erosion or mechanical damage occured at 1000hrs, 8kV no flashover, tracking No flashover, tracking erosion or mechanical damage occured at 1000hrs, 16kV no flashover, tracking No flashover, tracking erosion or mechanical damage occured at 1000hrs, 24kV no flashover, tracking

Order Reference:

For 11 kV Indoor Terminations (for XLPE Cable)

11 Kv 1 Core
Indoor
Terminations
Cable Size (mm2) Kit Code
1 x 16 - 50 XSES - 11 Enquire Now
1 x 70 - 120 XSES - 12 Enquire Now
1 x 150 - 300 XSES - 13 Enquire Now
1 x 400 - 630 XSES - 14 Enquire Now
1 x 800 - 1000 XSES - 15 Enquire Now

For 11 kV Outdoor Terminations (for XLPE Cable)

11 Kv 1 Core
Outdoor
Terminations
Cable Size (mm2) Kit Code
1 x 25 - 50 XSOS - 11 Enquire Now
1 x 70 - 120 XSOS - 12 Enquire Now
1 x 150 - 300 XSOS - 13 Enquire Now
1 x 400 - 630 XSOS - 14 Enquire Now
1 x 800 - 1000 XSOS - 15 Enquire Now

For 22 kV Indoor Terminations (for XLPE Cable)

22 Kv 1 Core
Indoor
Terminations
Cable Size (mm2) Kit Code
1 x 16 - 50 XSES - 21 Enquire Now
1 x 70 - 150 XSES - 22 Enquire Now
1 x 185 - 300 XSES - 23 Enquire Now
1 x 400 - 630 XSES - 24 Enquire Now
1 x 800 - 1000 XSES - 25 Enquire Now

For 22 kV Outdoor Terminations (for XLPE Cable)

22 Kv 1 Core
Outdoor
Terminations
Cable Size (mm2) Kit Code
1 x 16 - 50 XSOS - 21 Enquire Now
1 x 70 - 150 XSOS - 22 Enquire Now
1 x 185 - 300 XSOS - 23 Enquire Now
1 x 400 - 630 XSOS - 24 Enquire Now
1 x 800 - 1000 XSOS - 25 Enquire Now

For 33 kV Indoor Terminations (for XLPE Cable)

33 Kv 1 Core
Indoor
Terminations
Cable Size (mm2) Kit Code
1 x 25 - 50 XSES - 31 Enquire Now
1 x 70 - 185 XSES - 32 Enquire Now
1 x 240 - 400 XSES - 33 Enquire Now
1 x 500 - 800 XSES - 34 Enquire Now
1 x 1000 XSES - 35 Enquire Now

For 33 kV Outdoor Terminations (for XLPE Cable)

33 Kv 1 Core
Outdoor
Terminations
Cable Size (mm2) Kit Code
1 x 25 - 50 XSOS - 31 Enquire Now
1 x 70 - 185 XSOS - 32 Enquire Now
1 x 240 - 400 XSOS - 33 Enquire Now
1 x 500 - 800 XSOS - 34 Enquire Now
1 x 1000 XSOS - 35 Enquire Now
Send Message